Fault Code Reference

Sigenergy Fault Codes

Sigenergy hybrid inverters and all-in-one storage systems. Covers SigenStor and SigenEnergy products widely installed in UK residential and commercial solar projects.

71
Fault codes
Inverter (71)

Common fault codes

1001
Software Version Mismatch
Attempt the firmware upgrade again via the mySigen App
1002
Low Insulation Resistance
Check DC cable for short circuits or broken cables. Check positive and negative …
1003
Over-Temperature
Machine will normally restart after temperature returns to normal. Check ventila…
1004
Equipment Fault
Give standby/shutdown instruction. Disconnect DC and AC switches. Wait a few min…
1005
System Grounding Fault
Check whether the protective ground wire is connected normally
1006
PV String Overvoltage
Machine will restart after environment returns to normal. Measure PV voltage of …

All Sigenergy fault codes

1001
Software Version Mismatch
Attempt the firmware upgrade again via the mySigen App
1002
Low Insulation Resistance
Check DC cable for short circuits or broken cables. Check positive and negative …
1003
Over-Temperature
Machine will normally restart after temperature returns to normal. Check ventila…
1004
Equipment Fault
Give standby/shutdown instruction. Disconnect DC and AC switches. Wait a few min…
1005
System Grounding Fault
Check whether the protective ground wire is connected normally
1006
PV String Overvoltage
Machine will restart after environment returns to normal. Measure PV voltage of …
1007
PV String Reverse Connection
Wait for PV string current to drop below 0.5A. Disconnect DC switch. Correct pol…
1008
PV String Sinking Current
Check whether alarm string has fewer panels than other strings. If so, wait for …
1009
AFCI Fault
Turn off DC switch. Inspect faulty string for cable damage, poor connector conta…
1010
Grid Power Outage
Inverter will reconnect automatically when grid returns. Check whether grid supp…
1011
Grid Overvoltage
Inverter will reconnect when grid returns to normal. Measure actual grid voltage
1012
Grid Undervoltage
Inverter will reconnect when grid returns to normal. Measure actual grid voltage
1013
Grid Overfrequency
Inverter will reconnect when grid returns to normal. Measure actual grid frequen…
1014
Grid Underfrequency
Inverter will reconnect when grid returns to normal. Measure actual grid frequen…
1015
Grid Voltage Imbalance
Inverter will reconnect when grid returns to normal. Measure actual grid voltage…
1016
DC Component of Output Current Out of Limit
If occasional, likely caused by transient environmental change. Equipment will r…
1017
Leak Current Out of Limit
If occasional, likely caused by transient environmental change. Equipment will r…
1018
Communication Fault
ID1: Check 4G data balance, recharge if needed. ID2/ID3/ID4: Restart device. Che…
1019
Internal Protection
If occasional, may be caused by transient environmental change. Equipment will r…
1020
Abnormal AFCI Self-Checking Circuit
In APP: clear AFCI self-test circuit abnormality. Restart device and wait for re…
1021
Inverter AC Side Voltage Abnormal
ID1: Reduce load power. ID2: Check for AC output short circuit. ID3: Reduce gene…
1022
Manual Operation Protection / Rapid Shutdown
Confirm there are no safety hazards on site before resetting. Press emergency st…
1023
Neutral Line Loose or AC Wiring Abnormal
Isolate inverter (AC off, DC off). Check neutral terminal at AC connection block…
1024
Abnormal Phase Sequence
Adjust the sequence of the three-phase wiring on the AC output side
1025
Short Circuit to PE
Check for phase-to-ground short circuit on the grid side wiring
1026
Soft Start Failure
If occasional, equipment will return to normal automatically after environment s…
1027
Grid Frequency Unstable
If occasional, caused by instantaneous grid frequency fluctuation. Equipment wil…
2001
Software Version Mismatch
Upgrade system software again via APP
2002
Energy Storage Module Low Insulation Resistance
Issue standby/shutdown command via APP. Disconnect DC and AC switches. Wait a fe…
2003
Over-Temperature
Check ventilation at installation location is good and not obstructed
2004
Equipment Fault
Issue standby/shutdown command via APP. Disconnect DC and AC switches. Wait a fe…
2005
Under-Temperature
Wait for system self-heating to bring battery to operating temperature range. Fa…
2006
Battery Module Over-Voltage
Battery module or cells have too high a voltage — battery may be overcharged.
2007
Battery Module Under-Voltage
Battery module or cells have too low a voltage — may be caused by prolonged stor…
2008
Internal Protection
If occasional, may be caused by transient environmental change. Equipment will r…
3001
Software Version Mismatch
Upgrade again via APP
3002
Over-Temperature
Check ventilation at installation location is good and improve if needed
3003
Equipment Fault
Issue standby/shutdown command via APP. Disconnect DC and AC switches. Wait a fe…
3004
Too High Off-Grid Output Leak Current
Check load for insulation damage
3005
Neutral Point Grounding Fault
Check functional ground is effectively connected to external ground
3006
Abnormal Phase Sequence of Power Grid Wiring
Check wiring at the power grid input terminal is correct
3007
Load Side Wiring Phase Sequence Abnormal
Check load side wiring is correct
3008
Grid Phase Loss
Check terminal wiring on grid side — confirm all three-phase grid voltages are c…
3009
Grid Failure
Check grid voltage/frequency. If grid is abnormal, wait for grid to return to no…
3010
Generator Failure
Check generator voltage/frequency. If generator is abnormal, wait for it to retu…
3011
Load Fault
Check load frequency/voltage. If load is abnormal, wait for return to normal — a…
3012
Abnormal Phase Sequence of Engine Connection
Check wiring at oil machine input terminal is correct
3013
Emergency Shutdown
Cancel emergency shutdown signal when system returns to normal
3014
Bypass Switch Open
Check equipment is functioning normally. If Gateway is abnormal, disconnect inve…
3015
Bypass Switch On
Check equipment is functioning normally. If Gateway is abnormal, disconnect inve…
3016
Contactor Coil Overvoltage
Disconnect grid switch (air switch) via app and wait a few minutes
3017
Cabinet Door Opens
Verify cabinet door is fully closed and latched
3018
Frame Circuit Breaker Overcurrent Protection
Reduce load power on the affected circuit
3019
Frame Circuit Breaker Service Life Exceeded
Contact professional staff to replace breaker
4001
Communication Fault
ID1: Check Gateway communication interface is reliably connected. Confirm intern…
4002
CT Wiring Anomaly
Verify CT connections match installation diagram exactly
4003
Diesel Generator Startup Failure
Engine start anomaly — generator failed to start when called by system.
4004
CLS Fault
Manually clear via App interface
4005
Feed-in Power Limit Hard Protection
Check if anti-backflow protection is enabled in settings
4006
DI Custom Fault
ID1: Check for system grounding faults. ID2: Check meter communication and verif…
5001
Equipment Protection
ID1/ID2: Charger reconnects when grid returns to ±20%. Measure actual grid volta…
5002
Equipment Fault
Restart the charging pile. Check whether fault is eliminated
5003
Over-Temperature
Check whether charger is in direct sunlight. Check for nearby heat sources. Conf…
5004
Charging Cable Fault
Remove charging cable. Use multimeter to measure resistance between PP and PE. E…
5005
Meter Communication Fault
Check RS485 cable between charging pile and meter is connected correctly
5101
Software Version Mismatch
Upgrade again via mySigen App
5102
Low Insulation Resistance
Check DC cable for short circuit or broken cable. Check positive and negative po…
5103
Over-Temperature
ID1: Check ventilation, check for direct sunlight, check fan is functioning norm…
5104
Equipment Fault
ID1: Check fan connector is seated. Check for abnormal noise or blade deformatio…
5105
Charging Fault
ID1: Check charging plug is seated. Check CP circuit. ID2/ID3: Check for control…
5106
Equipment Protection
If occasional, may be caused by environmental changes or special working conditi…