Sigenergy
1023
Neutral Line Loose or AC Wiring Abnormal
Neutral conductor is not firmly connected, or AC wiring has an abnormality.
Common causes
Loose neutral connection at AC terminalAC wiring error — incorrect terminationN conductor missing or broken
What to check
STEP 1
Isolate inverter (AC off, DC off). Check neutral terminal at AC connection block — confirm firmly torqued (M5: 2.0 N·m)
STEP 2
Check neutral wiring from consumer unit to inverter — confirm continuity and correct termination
Escalate if
Neutral connection confirmed correct and fault persists — contact Sigenergy support via mySigen App > Support > Troubleshooting