Sigenergy
1002

Low Insulation Resistance

PV string short circuited to PE, or PV string installed in a chronically humid environment.

DC cable short circuit or broken cablePositive/negative poles shorted to groundChronic moisture at installation location
STEP 1
Check DC cable for short circuits or broken cables. Check positive and negative poles are not shorted to ground
STEP 2
If fault occurs on rainy days, recheck after weather improves. Check ISO impedance protection value in APP meets local regulations
Cables are normal and fault persists in dry conditions — submit fault feedback via APP > Service > Troubleshooting