Profile Mismatch

Grid Profile Does Not Match Detected Grid

The applied grid profile settings do not match the actual grid parameters measured by the microinverters.

Wrong G98/G99 profile selected at commissioningProfile applied to some MIs but not allGrid profile reset after a firmware update
STEP 1
Open Installer Toolkit, go to Grid Profile. Verify UK G98 (below 3.68kW export) or UK G99 (above 3.68kW, DNO approved) is applied to ALL microinverters on site
STEP 2
After applying correct profile, verify all MIs accept it. Check for any MIs still showing Profile Not Set in Enlighten
Correct profile applied but mismatch persists on specific MIs -- firmware update may be required, or those MIs may have a profile acceptance issue, escalate