G98/G99 Trip

G98/G99 Grid Disconnect Event

Microinverter(s) have disconnected due to a G98/G99 protection event (over/under voltage or frequency).

Voltage or frequency excursion on gridExport causing voltage rise above G98 limitG99 settings incorrectly configured
STEP 1
Check Enlighten for the time of the disconnect event. Cross-reference with grid voltage/frequency at that time
STEP 2
For G99 sites, verify grid protection settings are set per DNO approved parameters. Check export limit is active
Events are frequent and grid parameters are confirmed within normal range — G98/G99 protection settings may need DNO recertification