EV: Solid Red
IQ EV Charger 2 — Fault State
IQ EV Charger 2 LED bar is solid red — charger has detected a fault and stopped. Check grounding and phase wiring.
Common causes
Earth (PE) fault — charger requires solid earth connectionPhase wiring faultUpstream RCD has trippedInternal charger fault
What to check
STEP 1
Check the upstream MCB/RCBO feeding the charger has not tripped. Check earth continuity from charger housing to consumer unit earth bar (must be <1Ω)
STEP 2
Check phase wiring is correctly connected (L=Brown, N=Blue, PE=Green/Yellow). If RCBO upstream has tripped, identify the cause before resetting
Escalate if
Earth confirmed, MCB set, wiring correct but solid red persists — internal charger fault, escalate to Enphase support