Bat Not Dchg
IQ Battery Not Discharging
IQ Battery 5P will not discharge to support loads or export.
Common causes
Battery SoC is at or below the minimum reserveStorm Guard/Grid Outage Reserve is activeDischarge schedule not configuredBattery temperature fault
What to check
STEP 1
Check SoC in Enlighten. If at minimum reserve (default 20%), battery is protecting itself — increase PV/grid charge first
STEP 2
Check Enphase app for Storm Guard or Reserve settings. Confirm discharge schedule is enabled for current time period
Escalate if
SoC is above reserve, no Reserve mode active, but battery still will not discharge — escalate