Enphase
5P: G100 Lockout

G100 Export/Import Violation Lockout

The system has triggered more than 3 G100 compliance violations (export or import limit exceeded) in a 30-day period and has been locked out.

Incorrectly set export limit in Enphase appGrid profile not set correctly for DNO requirementsHigh import events from heat pump or EV charger tripping import limit
STEP 1
This lockout can only be cleared by Enphase Support — call +44 1908 828 928. Do not attempt to power cycle to clear, this will not work
STEP 2
After lockout is cleared, review and correct G100 export and import limit settings in the Enphase app. Ensure limits match the DNO approval
Always escalate G100 lockout — requires Enphase Support to unlock remotely. Up to 3 self-clearing violations per 30 days are permitted before lockout