ZP-017

Grid Sensor Error! / Fault Code (4)4

Grid CT incorrectly installed or reading incorrectly. Zappi cannot accurately measure grid import/export.

CT arrow pointing wrong directionCT on wrong cable — not main grid incomerMore than one Grid CT set — conflictCT clipped around wrong conductors
STEP 1
Check CT arrow — must point toward consumer unit (direction of import). CT must be on main grid incomer, upstream of ALL loads and ALL generation.
STEP 2
Check Zappi Linked Devices — only ONE CT set to GRID across entire installation. Remove any duplicate Grid CT assignments.
CT correct direction, correct position, only one Grid CT, error persists — contact myenergi support