Grid Sensor Error! / Fault Code (4)4
Grid CT incorrectly installed or reading incorrectly. Zappi cannot accurately measure grid import/export.
Common causes
CT arrow pointing wrong directionCT on wrong cable — not main grid incomerMore than one Grid CT set — conflictCT clipped around wrong conductors
What to check
STEP 1
Check CT arrow — must point toward consumer unit (direction of import). CT must be on main grid incomer, upstream of ALL loads and ALL generation.
STEP 2
Check Zappi Linked Devices — only ONE CT set to GRID across entire installation. Remove any duplicate Grid CT assignments.
Escalate if
CT correct direction, correct position, only one Grid CT, error persists — contact myenergi support