Growatt
Error 306

Grid Frequency Out of Range

Grid frequency has gone outside the G98/G99 permitted range (47--52 Hz) and the inverter disconnected for compliance.

Grid frequency event on the distribution networkGenerator or UPS on site causing frequency instabilityTest equipment interfering with supply
STEP 1
Check if any generator or UPS is running on site. Grid frequency events are typically brief -- inverter should auto-reconnect within minutes
STEP 2
Log event times. If recurring at specific times, report to DNO as a supply quality complaint
Occurs repeatedly (more than once daily) with no obvious local cause -- log and report to DNO
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath