Error 303

PE Abnormal / Earth Fault

Earth continuity test has failed or PE conductor is absent.

PE conductor not connected at inverter or isolatorPoor earth connection at consumer unitDamaged AC cable with broken earth
STEP 1
Test earth continuity from inverter PE terminal to consumer unit earth bar. Must be <1 Ω
STEP 2
Check AC cable for damage. Ensure PE terminal is clamped correctly at both ends
Earth continuity confirmed and fault persists — escalate