Growatt
Error 205
PV String Balance / Ground Fault
Differential leakage or balance fault detected between PV1 and PV2 inputs.
Common causes
One string has higher leakage than the otherPanel junction box seal failure on one stringCable insulation damage on one string only
What to check
STEP 1
Perform per-string IR test at 500V DC. The string with lower resistance is the leaky one. Inspect MC4 connectors and junction boxes on that string
STEP 2
Temporarily operate on one string only to confirm which string carries the fault
Escalate if
Both strings pass IR test but fault persists on reconnection -- may indicate inverter input circuit issue, escalate