Growatt
ARK: Insul Prot

Insulation Resistance Protection

DC isolation between battery terminals and earth is below the safe threshold (typically <50kΩ). BMS ALM LED shows red steady.

Damaged DC cable insulationMoisture in battery DC output connectorBattery enclosure damaged allowing moisture ingress
STEP 1
Disconnect battery from inverter. Use an insulation resistance tester (500V DC) to test resistance between positive terminal and earth, and negative terminal and earth. Any reading below 1MΩ indicates a fault
STEP 2
Inspect DC output cable and connector for damage or moisture. Check battery enclosure for physical damage
DC wiring tests OK but fault persists — internal battery insulation fault. Do not re-energise — safety risk. Escalate immediately
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath

More Growatt fault codes

Error 200
AFCI — Arc Fault Detected
Error 201
Leakage Current High
Error 202
PV Voltage Too High
Error 203
PV Isolation Low (RISO)
Error 300
AC Voltage Out of Range