Cell temperature above charging temperature protection threshold. Charging halted. BMS ALM LED flashes green.
Common causes
Ambient temperature above 45°CBattery in direct sunlightInsufficient ventilation clearances
What to check
STEP 1
Check ambient temperature at battery location. ARK operating range: 0–55°C discharge, 0–45°C charge. Ensure 300mm clearance on all sides. Remove from direct sunlight
STEP 2
Allow battery to cool and charging will resume automatically. Fault self-clears when temperature returns to safe range
Escalate if
Fault occurs in ambient temperatures below 35°C with adequate ventilation — NTC sensor fault, escalate
Need full interactive diagnosis?