ARK: Cell Volt Diff

Cell Voltage Difference Too Large

The spread between the highest and lowest cell voltages in the pack exceeds the permitted threshold.

Cells aging at different ratesBattery never reaching 100% SOC (balancing inhibited)One or more cells beginning to fail
STEP 1
Allow a full charge/discharge cycle to 100% SOC — passive balancing only operates at high SOC. In ShinePhone, ensure SOC target is set to 100% for this cycle
STEP 2
Monitor cell voltage spread over several cycles via ShinePhone. A spread that narrows after full cycles indicates balancing is working. A spread that continues to widen indicates a failing cell
Spread exceeds 500mV after multiple full charge cycles — cell failure, escalate for module replacement