ARK: Cell OV Alarm

Cell Over-Voltage Alarm

One or more cells approaching over-voltage protection threshold. Charging will derate. BMS ALM LED flashes green.

Cell imbalance after many charge cyclesInverter charge voltage set too highBattery not reaching full SOC regularly preventing balancing
STEP 1
Allow a full charge cycle to maximum SOC — passive cell balancing only operates at high SOC (above ~95%). Check charge voltage setpoint in ShinePhone matches ARK spec
STEP 2
Monitor individual cell voltages in ShinePhone advanced view. If cell spread >200mV, allow several full cycles for balancing to act
Alarm persists across multiple full charge cycles with spread still >500mV — cell failure, escalate