Tigo
TS4-01

Module Grey Icon / Not Discovered

TS4 unit not found during Discovery. Module appears grey in EI Portal. Optimisation and RSD not active for this unit.

Panel voltage below 16V minimum (shading, bypass diodes)Unit previously commissioned on another system — needs re-assignmentTAP out of range or not transmittingSerial number not entered in EI App Equipment page
STEP 1
Confirm CCA/TAP running. Confirm all serial numbers entered in EI App. Wait 60 minutes after sunrise.
STEP 2
Measure panel voltage — must be ≥16V for TS4 to power on. Run Discovery: EI App > Start Discovery.
16V confirmed, serial numbers entered, TAP working, unit still grey after 24 hours — contact Tigo support (may need re-assignment from previous system).