Sungrow
SG-016 · ID 88

Electric Arc Fault (AFCI)

Arc fault detected on PV DC side. AFCI protection has triggered — potentially dangerous electrical arc in DC wiring. Displayed fault ID: 088.

Damaged DC cable creating arc conditionLoose connection at DC terminal, fuse, or combinerBurnt or damaged component in DC circuit
STEP 1
Disconnect DC switch to OFF. Inspect all DC cables for visible damage — cuts, abrasion, pinching, or burning. Check DC terminals, fuses, and combiners for loose connections.
STEP 2
Replace damaged cables or components. Fasten any loose terminals. Reconnect DC supply. Clear electric arc fault via App or LCD screen.
No visible damage found or fault returns after clearing — contact Sungrow support