Inverter cannot detect utility grid — islanding protection triggered. One of the most common Sungrow faults. Auto-reconnects when supply restored. Displayed fault ID: 010.
Common causes
Genuine grid outage or blackoutAC circuit breaker between inverter and grid is openLoose or incorrectly wired AC cable (live/neutral swap)AC cable not firmly connected to terminal
What to check
STEP 1
Check whether grid is supplying power — test other loads in property. Confirm AC circuit breaker is closed (ON).
STEP 2
Inspect AC cable — confirm firmly connected at both inverter terminal and distribution board. Verify live and neutral are not swapped.
Escalate if
Grid confirmed present, cabling confirmed correct, fault still active — contact Sungrow support