SG-001 · IDs 2,3,14,15

Grid Overvoltage

AC grid voltage exceeds upper protection threshold. Inverter disconnects. Auto-reconnects when voltage returns to normal. Displayed fault ID: 002, 003, 014, 015.

Utility grid voltage genuinely elevatedOvervoltage protection set too lowLong or undersized AC cable causing voltage rise under export
STEP 1
Wait — inverter auto-reconnects. If recurring, measure actual grid voltage at AC terminals with calibrated multimeter.
STEP 2
If measured voltage exceeds set protection value, contact DNO/DNSP. Do not modify protection parameters without written DNO consent.
Fault persists after grid voltage confirmed normal and protection parameters reviewed — contact Sungrow support