Sungrow
SG-014 · IDs 1548–1579

String Current Reflux

Current flowing backwards through one or more PV strings — mismatch in string configuration or shading causing reverse current.

Affected string has fewer PV modules than other stringsPV module heavily shaded causing reverse biasModule open-circuit voltage abnormalIncorrect panel orientation on affected string
STEP 1
Identify affected string. Check if module count is lower than other strings on same MPPT. If so: wait for current <0.5 A, disconnect DC switch, rebalance string configuration.
STEP 2
Check for shading on string — remove obstruction if possible. Measure each string's Voc with DC switch disconnected. Confirm all modules face correct orientation.
String configuration and shading confirmed correct but alarm persists — contact Sungrow support