Solis
PvMidIso

PV Midpoint Insulation Low (Alarm 1029)

PV middle point insulation protection. PVGndRun variant means a PV terminal is grounded during operation.

Morning dew or rain lowering insulationDamaged string cable insulationN to PE connection issue
STEP 1
Note the timing. Early morning, late afternoon or rainy day reports are usually moisture and clear when dry.
STEP 2
Measure string to earth resistance, it should be above 20 kOhm. Investigate the string cabling if low.
Resistance healthy and dry weather but alarm persists, try a firmware update first
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath

More Solis fault codes

E001
Grid Over-Voltage
E002
Grid Under-Voltage
E003
Grid Over-Frequency
E004
Grid Under-Frequency
E005
Grid Impedance High