Solis
E001

Grid Over-Voltage

Grid voltage has exceeded upper limit. Inverter disconnects to protect equipment.

DNO voltage too high at point of connectionLong AC cable run causing voltage riseGrid voltage fluctuation
STEP 1
Measure grid voltage at inverter AC terminals with multimeter. UK nominal 230V — if consistently above 253V, this is a DNO issue
STEP 2
Check AC cable sizing and length. Voltage rise on long runs — resize cable if needed. Log voltage and time to report to DNO
Voltage within spec but fault persists, or voltage consistently above 253V — report to DNO and contact Solis support