Solis
PV ISO-PRO

PV Insulation Protection (Alarm 1033)

Low PV insulation. PV ISO-PRO 01 is negative to ground, PV ISO-PRO 02 is positive to ground.

Morning dew or rain lowering insulationDamaged PV cable insulationN to PE connection issueOutdated firmware threshold
STEP 1
Note the timing. Morning, late afternoon or rain reports are usually moisture and clear when dry.
STEP 2
Measure string to earth resistance, it should be above 20 kOhm. Re-cable the string if low.
All checks pass but alarm persists in dry conditions