E041

Export Limit Exceeded

Inverter has detected export above the set limit. This may be a DNO compliance issue.

Export limit set incorrectly in Solis appCT clamp misreadingLoad suddenly reduced causing export spike
STEP 1
Check export limit setting in Solis app. G98 installs: typically 3.68 kW limit. G99: as per DNO approval letter
STEP 2
Confirm CT clamp is positioned correctly — must read grid connection accurately
Export limit correct and CT correct but export still exceeding — contact Solis support