Solis
E040
Export Limit Fault — CT Clamp
Export limiting CT clamp not reading correctly. Inverter cannot determine grid export level.
Common causes
CT clamp not installedCT clamp reversedCT clamp on wrong cableCT cable disconnected
What to check
STEP 1
Locate export limit CT clamp — must be on grid incomer (DNO side of consumer unit). Arrow must point toward consumer unit
STEP 2
Check CT cable is connected to inverter CT input. Check Solis app — grid reading should show live import/export value
Escalate if
CT installed correctly and connected but grid reading zero — CT or input port fault, contact Solis support