Solis
E022
Battery Under-Voltage
Battery pack voltage has dropped below minimum safe level.
Common causes
Battery deeply dischargedDischarge cut-off set too lowBMS fault
What to check
STEP 1
Check inverter battery discharge cut-off voltage setting. Dyness Powerbox G2: minimum 44V. Fogstar Drift 16kWh: minimum 44V
STEP 2
Attempt to charge battery from grid — set inverter to forced charge mode in Solis app
Escalate if
Battery won't accept charge, voltage continues dropping — BMS fault, contact battery manufacturer