Solis
E012

Low Insulation Resistance

Insulation resistance between PV array and earth below safe threshold. Possible DC cable fault.

DC cable damaged or pinchedPanel junction box faultWet conditions causing temporary resistance drop
STEP 1
Check DC cables along full run for damage, crushing, or abrasion. Check panel junction boxes
STEP 2
If fault occurs in wet weather, monitor — may self-resolve when array dries. Re-test insulation resistance with system off
Cables and junction boxes clear, fault persists in dry conditions — panel or underground cable fault
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath

More Solis fault codes

E001
Grid Over-Voltage
E002
Grid Under-Voltage
E003
Grid Over-Frequency
E004
Grid Under-Frequency
E005