FoxESS
EP: Deep Discharge

Battery Deeply Discharged — Recovery Required

EP battery SOC has reached 0% and has been left without charging. Risk of permanent capacity damage.

Extended grid outage draining batteryMinimum SOC not setBattery left disconnected from charge source for extended period
STEP 1
Connect to a charge source immediately. Force-charge via inverter if needed. Check if any EP SOC LEDs illuminate — if none light up even at full AC power, the battery may be too deeply discharged to self-recover
STEP 2
The EP series has a 7-day deep discharge limit — if left at 0% for >7 days, permanent capacity loss occurs. Document the timeline for warranty assessment
Battery will not accept charge after 4 hours connected to charge source — deep discharge damage, escalate for warranty assessment