ECS: Over Voltage

Pack Over-Voltage Fault

Battery pack voltage has exceeded the maximum threshold. Charging interrupted.

Inverter charge voltage set too high for the battery modelCell imbalance causing one cell to overchargeBMS charge control failure
STEP 1
Check inverter battery charge voltage setting in Fox Cloud matches the ECS battery model spec (e.g. ECS2900-H2: max 131.4V, ECS4100-H7: max 459.9V)
STEP 2
Power cycle battery (DC switch off → hold POWER button 5s → DC switch on). Monitor charge voltage in Fox Cloud after restart
Voltage is above maximum under light or no-load — cell or BMS fault, escalate