SolarEdge
18x / F-Isolation

DC Isolation Fault (Ground Leakage)

DC insulation fault detected — ground leakage on PV string or cable. Inverter will not produce until cleared. This is a safety protection. Fault code appears as 18x (residential) or F-Isolation in SetApp.

Damaged PV cable insulationWater ingress into MC4 connectorGround fault in PV arrayIncorrect grounding of DC conductors
STEP 1
Check all DC cables for visible damage, pinch points, or rodent damage. Inspect MC4 connectors for moisture or corrosion.
STEP 2
Test string insulation resistance with a megohmmeter — each string should show >1 MΩ to earth. Identify the affected string via SetApp Device List.
No visible damage, all strings >1 MΩ, fault persists after dry conditions — contact SolarEdge support. Use decision tree se_isolation_fault for full diagnostic path.
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath

More SolarEdge fault codes

2xF
DC Overvoltage Error
2x10
Vref Voltage Error
2x11
Over Temperature
2x13
Software Error
2x18
Broken or Unconnected Temperature Sensor