Anker
CT-ERR

CT / Power Sensor Error

Power sensor (CT clamp on grid incomer) not detected or reading incorrectly.

CT clamp cable disconnected at inverter RS485 portCT clamp not clamped around conductorCT arrow facing wrong direction (reversed import/export)RS485 cable damaged
STEP 1
Confirm CT clamp cable is plugged into RS485 port on inverter
STEP 2
Confirm CT clamp is around the grid incomer L conductor only (not L+N together)
CT correctly installed and cabled, fault persists -- try replacing CT clamp; contact Anker support