Anker
GRID_FAULT

Grid Fault / Grid Abnormal

Grid voltage or frequency outside tolerance — system has disconnected.

Grid undervoltage (<207 VAC single-phase)Grid overvoltage (>253 VAC single-phase) — common in summer near substationsGrid frequency outside 47–53 HzDNO planned outage or local faultLoose AC grid connector at power moduleThree-phase: phase imbalance or missing phase
STEP 1
Measure AC voltage at AC GRID port — should be 230 VAC ±10%
STEP 2
Measure grid frequency — should be 50 Hz ±3 Hz
Voltage consistently >253 VAC — report to DNO. Voltage in range but fault persists — contact Anker support