CT Fault
SolaX
CT Fault
CT / Smart Meter Fault (IE 37)
CT clamp or smart meter fault -- inverter cannot read grid import/export.
Common causes
CT on wrong cable (must be L only)
CT arrow pointing wrong way
CT cable disconnected
CT cable run too long (over 100m)
What to check
STEP 1
Check CT is on L wire only, arrow pointing toward grid. Check CT connection at inverter (CT1_1 = Pin 1, CT1_2 = Pin 8). LCD > Menu > Meter/CT Check.
Escalate if
CT placement and wiring confirmed correct but Meter Fault persists
Need full interactive diagnosis?
Faultpath walks you through decision trees, fault codes, and commissioning — built for solar & battery engineers.
Open Faultpath